KAC-AD6-R
AI

The **KAC-AD6-R** is an addressable input module (often referred to as a "Single Input Module" or "Switch Monitor") primarily used in fire alarm systems, specifically designed to interface with **KAC** and **Morley-IAS** protocol panels.
---
## 1. Technical Specifications
The following table highlights the core electronic characteristics of the KAC-AD6-R:
| Parameter | Specification |
| :--- | :--- |
| **Operating Voltage** | 15V to 30V DC (Loop Powered) |
| **Quiescent Current** | ~350μA (Typical) |
| **Alarm Current** | ~2.8mA (LED On) |
| **Communication Protocol** | Addressable (Analog) |
| **End of Line (EOL)** | 47kΩ Resistor |
| **Operating Temperature** | -10°C to +60°C |
---
## 2. Key Electronic Components & Functions
### A. The Addressable ASIC
The heart of the module is an **Application-Specific Integrated Circuit (ASIC)**. This chip manages the digital communication with the Fire Alarm Control Panel (FACP). It translates the analog voltage state of the input circuit into a digital data packet sent via the signaling line circuit (SLC).
### B. Rotary Addressing Switches
Unlike some modern modules programmed via software, the KAC-AD6-R typically uses **two rotary switches** (decadic switches) to set the module's unique address.
* **Switch 1:** Tens digit (0-9)
* **Switch 2:** Units digit (0-9)
* *Example:* Setting Tens to 2 and Units to 5 assigns address 25.
### C. Input Monitoring Circuit
The module monitors a single circuit of dry-contact devices (e.g., flow switches, pressure switches, or non-addressable pull stations).
* **Supervision:** It uses an **End-of-Line (EOL) resistor**.
* **Logic:** The electronics detect three states:
1. **Normal:** Correct resistance detected.
2. **Alarm:** Short circuit (via a trigger resistor).
3. **Fault:** Open circuit (wire cut).
### D. Integrated LED Indicator
A built-in LED provides visual feedback of the module's status:
* **Blinking (Green/Red):** Communication polling from the panel.
* **Steady Red:** Alarm/Active state.
---
## 3. Wiring Configuration
The electronics are designed for a simple 4-terminal connection:
```text
[ LOOP IN + ] --- [ Terminal 1 ]
[ LOOP IN - ] --- [ Terminal 2 ]
[ INPUT + ] --- [ Terminal 3 ] --- (External Switch) --- [ 47k EOL ]
[ INPUT - ] --- [ Terminal 4 ] ------------------------- [ 47k EOL ]
```
---
## 4. Applications
The KAC-AD6-R is electronically designed to integrate non-addressable hardware into an intelligent loop:
* Monitoring **sprinkler flow switches**.
* Interfacing **extinguishing system** status.
* Monitoring **fire shutters** or damper positions.
- ⤷
What is the specific EOL resistor value required for the KAC-AD6-R?
- ⤷ How do you set the address on this module manually?
- ⤷ Is the KAC-AD6-R compatible with all addressable fire panels?